Commission of the valve:
Every valve is factory-set to a nominal temperature of 105°F. Every valve must be adjusted on-site to ensure correct delivery of the desired mixed water temperature, as installation conditions can vary site to site.
Outlet temperature range: 95-115°F(35-46℃)
Temperature, hot supply: 180°F max(82℃)
Temperature, cold supply: 40-80°F(4-27℃)
Temperature stability(nominal): +/-5 °F(+/- 2.8℃)
Temperature differential: +/- 10 °F(5.6℃)
Model: 1/2 CPVC;
Standard complying with: ASSE1017, ASSE1070;
Working pressure: 0.1bar-5bar;
Outlet temperature range: 95-115°F(35-46℃);
Temperature, hot supply: 180°F max(82℃);
Temperature, cold supply: 40-80°F(4-27℃);
Temperature stability(nominal): +/-5 °F(+/- 2.8℃);
Temperature differential: +/- 10 °F(5.6℃);
Factory setting temperature: 40.6℃;
Material: Lead Free;